Dark Light

[:en]DOL start, for motor with heavy starting duty[:ro]Pornirea directa, pentru actionari cu porniri grele[:] Leave a comment

[:en]

Operation mode: By pressing Start push button bridge contactor Q2 is energized and maintains itself via Q2 normal open auxiliary contact. At the same time, voltage is applied to the time ON delay T1 timer. The main contactor Q1 is energized by Q2 normal open auxiliary contact and maintains itself via Q1 normal open contact. When the set time – which corresponds to the start-up time of the motor – has elapsed, the bridging contactor Q2 is disconnected by T1 and can only be energized again after the motor has been switched off by pressing push button Stop. The normal close contact of Q1 prevents Q2 and T1 closing whilst the motor is running. When overload occur, normally closed contact 95-96 of thermal overload relay  TF1 is opened and the motor stops.

[:ro]

Modul de funcţionare: Prin acţionarea butonului Start se energizează contactorul punte Q2 si se automenţine prin contactul auxiliar normal deschis . Simultan se aplică tensiunea la releul de timp T1 si prin contactul normal deschis al Q2 este anclașat contactorul de reţea Q1 care se automenţine  prin contactul auxiliar normal deschis. După scurgerea temporizării fixate corespunzător timpului de pornire a motorului, contactorul de punte Q2 este deconectat. T1 își pierde și el alimentarea și poate fi energizat, la fel ca și Q2 după ce motorul a fost oprit prin apăsarea butonului Stop. Contactul normal închis al Q1 împiedică conectarea lui Q2 și T1 în timpul funcţionării. La suprasarcină se deschide contactul normal închis 95-96 al releului termic de protecţie FT1.

[:]

Leave a Reply

Notice: ob_end_flush(): Failed to send buffer of zlib output compression (0) in /home/dorinel/public_html/wp-includes/functions.php on line 5481